ADVANCED INSULATION KOREA Genuine & OEM spare parts made in Japan, China, Korea and Europe for Maritime, Oil & Gas Industry.
Contact us if you are looking for Fire Protection Materials ContraFlex JF120 marine equipment and ship spare parts.
Equipment: Fire Protection Materials
Manufacturer: ADVANCED INSULATION KOREA
Type / Model / Part no: ContraFlex JF120
Technical Specification & Spare Parts:
ContraFlex JF120 Fire Protection Materials ADVANCED INSULATION KOREA
fire Protection – Partitions & outfits,
Fire Protection Materials,
Fire Protection Materials,
Installation is to be as per the jet fire exposure tests performed on a Tubular Section (HP/A = 127/m) and a Panel Specimen, both fitted with a "ContraFlex" flexible fire resistant insulation jacket (61 mm total nominal thickness). , Suitable approved insulation is to be applied to any other part of the protected fire exposed surface not covered by the jacket, in all cases. Attention is to be paid to means of securing jacket boundaries and the prevention of heat bridging: an overlap of at least 150mm should be provided between two systems.,
Hydrocarbon Jet Fire Resistance (ISO 22899-1:2007) J-Rating | For Panel Specimen, temperature rise for assembly section | 11.9C after 15 minutes | 56.3C after 30 minutes | 106.2C after 45 minutes | 146.1C after 60 minutes | 198.4C after 90 minutes | 224.7C after 120 minutes | Blast Overpressure Resistance 2.15 bar | | For Tubular Specimen, temperature rise for assembly section | 13.3C after 15 minutes | 24.8C after 30 minutes | 35.2C after 45 minutes | 48.1C after 60 minutes | 83.0C after 90 minutes | 122.9C after 120 minutes | Blast Overpressure Resistance 2.15 bar,
ISO 22899-1:2007 "Determination of the Resistance to Jet Fires of Passive Fire Protection Materials, Part 1: General Requirements",
Contact our Customer Care Center today for quotations and orders.
Shipcare+ Japan
[email protected]
www.shipcare.jp